T-4101A (3-10kVA)

Banking and finance institutions maintain small to medium systems, many of which require individual power protection. An automated teller machine (ATM) is one of the typical systems which need an online UPS to protect from possible irregularities in its power supply. ATMs are now located everywhere – bank branches, office buildings, residential areas, supermarkets, to mention a few places. They are exposed to unstable utility power and prolonged power outages each and every day, which in turn leads to communications line interruption; switch servers shutdown and frozen screens, all leading to loss of transactions and high customer dissatisfaction levels.
The i-power T-4101A is a state of the art pure sine wave single-phase UPS system that employs a true online double-conversion technology, customised to ensure banking and finance business continuity. It is designed to deliver clean and high quality electrical power for all ATM applications. The T-4101A (1P/1P) comes with a built-in AVR and wide input voltage range that protects ATM devices against outages, disturbances and spikes. The T-4101A offers high output power factor of up to 0.9, ensuring high performance and efficiency for critical applications. In addition, the T-4101A comes with a smart battery charger that optimizes the battery performance, ensuring longer lasting battery life.

 

Product Highlights:

  • Wide input voltage range.
  • Built-in AVR functionality.
  • Built-in output isolation transformer.
  • Wide input frequency tolerance.
  • Real time user friendly LCD display.
  • Intelligent battery charger.
  • RS232 communication port.
  • Optional external battery bank for long backup time.
  • Optional UPS management software.
  • Optional external SNMP/USB/dry contacts.
  • Optional i-power Remote Management System (RMS) available.

Data Sheet

DownloadPDFButton

Brochure

DownloadPDFButton

Product Specifications:

Capacity3kVA/2.7kW (Customizable to 6KVA and 10KVA as well)
Input
Voltage (Vac)100 to 295 (L1, L2, G)
Frequency (Hz)50 ± 5%
Output
Power Factor0.9
Voltage (Vac)220±2%
Frequency (Hz)50±1% (Battery mode)
WaveformPure Sine Wave
Transfer time (ms)0
Isolation Built-in output transformer
Battery
Battery Votlage (Vdc)96
Battery TypeExternal
Charger Current (A) Max5
Other
Communication Interface RS232 (USB/Dry contacts/SNMP adaptor is optional
DisplayLCD indicates the status of UPS, input voltage, input frequency, output voltage, load % and bettery voltage
Alarmlow bettery, abnormal AC input, UPS failure
Porotection low bettery, overload, short circuit, over temperature
Input/output Connections One pin and two SA50 sockets for external battery cabinet
Input PlugUK plug
Output SocketsOne IEC sockets and two SA50 sockets for external battery cabinet
Cooling Forced cooling through fans
Working Temperature (°C)0 to 50
Relativite Humidity 0 to 95%, No condensation
Physical
Dimensions (WxDxH) (mm)198*670*347
Weight (Kg)48