Model |
R300140240S |
R300240240S |
R300340240S |
R300540240S |
R300840240S |
Power Rating (KVA) |
10KVA |
20KVA |
30KVA |
50KVA |
80KVA |
Technical Specifications |
Control Method |
Servo Motor (Microprocessor CPU) |
Input Rated Voltage |
3 x 400VAC (3Phase + N) |
Voltage Range |
400VC ±20% (Optional: ±25,±30%)) |
Frequency |
50/60 Hz |
Output Rated Voltage |
3 x 400VAC (3phase + N) |
Stabilizing Accuracy |
±1~5% Adjustable |
Power Factor |
PF >= 0.8 |
Efficiency |
>= 98% |
Response time |
<= 0.5S |
Delay time |
<= 5s(Optional) |
Waveform Distortion |
<= 1% |
Over Voltage |
Power cut off in 3-5s if Output voltage >10% |
Under Voltage |
Power cut off in 3-5s if Output voltage < 15% |
Overload |
Power cut off in 3-5s |
Phase Dislocation |
Alarm generated and Power Cut off |
Phase Loss |
Alarm generated and Power Cut off |
Short Circuit |
Power cut off |
Manual Bypass |
Available |
Digital Display |
Real-time display of input/output voltage, output currents |
Working Status |
AVR, Bypass, Fuse Blown, Over-voltage, Under-voltage,Over-load |
Cooling System |
Air Cooled |
Insulation Resistance |
>= 2M Ohm |
Noise |
<65dB/m |
Ambient Temperature |
0°C-45°C ( No condensation ) |
Humidity |
20%-90% |
Size WxDxH (mm) |
340x400x770 |
390×500×820 |
450×670×1050 |
500×770×1250 |
Net Weight (KG) |
65kg |
111kg |
125kg |
137kg |
270kg |
Gross Weight (KG) |
80kg |
126kg |
140kg |
157kg |
295kg |
Optional Features |
Input & Output breakers |
Outdoor Enclosure IP-54 |
EMI / RFI Filter |
Surge Protection |
Neutral & Phase Failure Protection |
Data Logging / Remote Monitoring |
Note: Product image and technical specifications are for reference and could be change without any notice. Custom built solutions are also available to meet specific requirements |