AVR-2002 Static 3-Phase (10-250k)

Call For Pricing

The i-power “Static Voltage Stabilizers” provide protection against main power sags, surges and brownouts. It is ideal for locations that are subject to inconsistencies in the main supply. Each stabilizer has a wide input voltage tolerance and has been designed to provide the ultimate reliability in hostile environments where the quality of the main supply cannot be guaranteed.

The Non- contact voltage stabilizer series adopts the latest DSP operation control technology, fastest AC sampling, effective values calibrating, current zero-crossing switching and fast compensating voltage stabilizing technology to meet the new generation technology requirements. This product is extremely suitable for equipment that require highly reliable and stable power supply or environments where high amplitude of voltage fluctuation is common.

Product Highlights

  • Non-contact based technology and free from abrasion & routine maintenance
  • Multi Info LCD Display
  • Precise output voltage regulation
  • Fast response time against input voltage fluctuations
  • Overload, Under/Over Voltage, Short Circuit, Bypass protection
  • Adapts smart CPU control technology to control all processes to increase system reliability.
  • All devices are fully tested and verified for maximum performance.

Application

  • Telecom
  • Medical
  • Industrial
  • Commercial
  • Household appliances
Model T300140240S T300240240S T300340240S T300540240S T300840240S
Power Rating (KVA) 10KVA 20KVA 30KVA 50KVA 80KVA
Technical Specifications
Control Method SCR/Non-Contact (Microprocessor CPU)
Input Rated Voltage 3 x 400VAC (3phase + N) (Optional: 380/415)
Voltage Range 400VC ±20% (Optional: ±25,±30%)
Frequency 50/60 Hz
Output Rated Voltage 3 x 400VAC (3phase + N) (Optional: 380/415)
Stabilizing Accuracy ±1~5% Adjustable
Power Factor PF >= 0.8
Efficiency >= 98%
Response time <= 0.06S
Delay time <= 5s(Optional)
Waveform Distortion <= 1%
Over Voltage Power cut off in 3-5s if Output voltage >10%
Under Voltage Power cut off in 3-5s if Output voltage < 15%
Overload Power cut off in 3-5s
Short Circuit Power cut off
Manual Bypass Available
Static Bypass Available
Digital Display Real-time display of input/output voltage, output currents
Working Status AVR, Bypass, Fuse Blown, Over-voltage, Under-voltage,Over-load
Cooling System Air Cooled
Insulation Resistance >= 2M Ohm
Noise <65dB/m
Ambient Temperature 0°C-45°C ( No condensation )
Humidity 20%-90%
Size WxDxH (mm) 380×780×830 430×780×1170
Net Weight (KG) 80kg 85kg 88kg 104kg 153kg
Note: Product image and technical specifications are for reference and could be change without any notice.
Custom built solutions are also available to meet specific requirements