Model |
T310040240S |
T312540240S |
T315040240S |
T320040240S |
T330040240S |
Power Rating (KVA) |
1000KVA |
1250KVA |
1500KVA |
2000KVA |
3000KVA |
Technical Specifications |
Control Method |
SCR/Non-Contac(t Microprocessor CPU)) |
Input Rated Voltage |
3 x 400VAC (3phase + N) (Optional: 380/415) |
Voltage Range |
400VC ±20% (Optional: ±25,±30%)) |
Frequency |
50/60 Hz |
Output Rated Voltage |
3 x 400VAC (3phase + N) |
Stabilizing Accuracy |
±1~5% Adjustable |
Power Factor |
PF >= 0.8 |
Efficiency |
>= 98% |
Response time |
<= 0.06S |
Delay time |
<= 5s(Optional) |
Waveform Distortion |
<= 1% |
Over Voltage |
Power cut off in 3-5s if Output voltage >10% |
Under Voltage |
Power cut off in 3-5s if Output voltage < 15% |
Overload |
Power cut off in 3-5s |
Phase Loss |
Alarm generated and Power Cut off |
Short Circuit |
Power cut off |
Manual Bypass |
Available |
Digital Display |
Real-time display of input/output voltage, output currents |
Working Status |
AVR, Bypass, Fuse Blown, Over-voltage, Under-voltage,Over-load |
Cooling System |
Air Cooled |
Insulation Resistance |
>= 2M Ohm |
Voltage-endurance |
The whole machine has no breakdown and no arcing phenomena for 2000VAC/ min. |
Noise |
<65dB/m |
Ambient Temperature |
0°C-45°C ( No condensation ) |
Humidity |
20%-90% |
Size WxDxH (mm) |
1500×1000×1950 |
1500×1300×1950 |
2000×1500×1950 |
1500× 1000× 2000 |
Net Weight (KG) |
1400 |
1600 |
2250 |
4200 |
7900 |
Gross Weight (KG) |
1600 |
1850 |
2500 |
4450 |
9480 |
Optional Features |
Input & Output breakers |
Outdoor Enclosure IP-54 |
EMI / RFI Filter |
Surge Protection |
Neutral & Phase Failure Protection |
Data Logging / Remote Monitoring |
Note: Product image and technical specifications are for reference and could be change without any notice. Custom built solutions are also available to meet specific requirements |