Model |
OH1001T80300S |
OH1002T80600S |
OH1003T80800S |
OH1006T91600S |
OH1010T91600S |
Capacity |
1KVA / 0.8KW |
2KVA / 1.6KW |
3KVA /2.4KW |
6KVA / 5.4KW |
10KVA / 9KW |
Technical Specifications |
UPS Structure |
Online Double Conversion - Tower Type |
Topology |
High Frequency, Transformer Less |
Overall Efficiency (AC-AC ) |
> 90% |
Noise(In 2 Meters) |
< 55dB |
Working Temp |
0-40℃ |
Storage Temp |
-15 ~ 60℃(Without BATs) |
Humidity |
< 95% Non Condensing |
Safety Standard |
GB/T14715; EN62040-1 |
EMC Standard |
EN 50091-1/2, EN62040-2 |
Protections |
Overload, Short-Circuit, Over Temp., Utility Power Voltage High/Low, BAT Voltage High/Low |
Generator Compatibility |
Available |
DC Start |
Available |
Manual Maintenance Bypass |
None |
Optional |
Display |
LCD/LED |
Alarm |
Auto |
Mute |
Auto |
ECO Mode |
Available |
Rectifier Specification |
Input Voltage Range |
110~300VAC ±5VAC (175-285VAC at full load) |
Input Frequency Range |
40Hz to 70Hz (Auto Sensing) |
Input PF |
0.99 |
THDI |
< 5% |
Output Specification |
Output Voltage |
220Vac |
Output PF |
0.8 |
0.9 |
Output Voltage Regulation |
220Vac±1% (Static Load); 220Vac±2% (50-0% Sudden Change); 220Vac±3% (100-0% Sudden Change) |
Output Freq. (BAT Mode) |
50Hz±0.2% |
Output Waveform |
Pure Sine Wave |
Distortion |
< 1%(Linear Full Load),< 3%(100% Non-Linear Load) |
Overload |
105 - 125% for 1 Minute 126 - 150%for 30 seconds |
105 - 125% for 10 Minutes 126 - 150% for 1 Minute |
Crest Ratio |
3:1 |
Efficiency |
> 90% |
Short-Circuit |
Circuit Auto Protection, Output Voltage/Current 0 |
Output Abnormal |
INV Output Auto-Locked Protection |
Noise Suppression |
EMI/RFI Wave Filter |
BAT Low |
Shutdown Protection |
Dynamic Response |
3% At Full Load,Recovering In 20ms |
Auto-Restart |
Available |
Software Control |
Available |
Bypass Specification |
Static Bypass Transfer Time |
0ms |
Static Bypass Range |
80Vac± 5%~285Vac±5% |
Bypass - INV Transfer Time |
2ms |
Battery Specification |
Model |
OH1001T80300S |
OH1002T80600S |
OH1003T800S |
OH1006T91600S |
OH1010T91600S |
Capacity |
1KVA / 0.8KW |
2KVA / 1.6KW |
3KVA /2.4KW |
6KVA / 5.4KW |
10KVA / 9KW |
Type |
Sealed Lead Acid Maintenance Free |
VDC |
36 |
72 |
96 |
192 |
Charging Current |
Max 4A |
Max 4A |
Max 4A |
Max 4A (10A Optional) |
Communication Specification |
Standard Communication Port |
Rs232 |
Optional |
SNMP/RS485/ Dry Contact |
Remote Software |
Multi-Functional Monitoring System, Online And BAT Mode Status, BAT Fault, Remote Control |
Physical Characteristics |
Dimensions In mm |
145X220X248 |
145X220X318 |
190X318X368 |
190X340X528 |
Net Weight Kg |
3.5 |
5.9 |
8.3 / 10 |
16 |
Note: Product image and technical specifications are for reference and could be change without any notice. |