It is a versatile, high quality, and cost-competitive UPS developed to handle a wide voltage range and inconsistent power conditions. The T-4002 series provides a safe power supply guaranteed for mission-critical applications such as computer equipment, telecommunication devices, precision instrument, network termination equipment, and more.

Product Highlights:

  • True online double-conversion topology and zero transfer time to battery provides 24/7 full-time protection.
  • USB/RS232 & RJ-11/RJ45 serial port interface (Optional).
  • All devices are fully tested and verified for maximum performance.
Model OH2010T81600S OH2015T81600S OH2020T81600S
Capacity 10KVA / 8KW 15KVA / 12KW 20KVA / 16KW
Model OH2010T92000S OH2015T92000S OH2020T91600S
Capacity 10KVA / 9KW 15KVA / 13.5KW 20KVA / 18KW
Host Machine Specification
UPS Structure Online Double Conversion - Tower Type
Topology High Frequency, Transformer Less
Overall Efficiency (AC-AC ) > 90%
Noise(In 2 Meters) < 50dB
Working Temp 0-40℃
Storage Temp -15 ~ 60℃(Without BATs)
Humidity < 95% Non Condensing
Safety Standard GB/T14715; EN62040-1
EMC Standard EN 50091-1/2, EN62040-2
Protections Overload, Short-Circuit, Over Temp., Utility Power Voltage High/Low, BAT Voltage High/Low
Generator Compatibility Available
DC Start Available
Manual Maintenance Bypass Optional
Display LCD/LED
Alarm Auto
Mute Auto
Rectifier Specification
Input Voltage Range 304 ~ 478Vac
Input Frequency Range 45-65Hz(Auto Tracking)
Input PF 0.99
THDI < 5%
Output Specification
Output Voltage 220Vac
Output PF 0.8/0.9
Output Voltage Regulation 220Vac±1%(Static Load);220Vac±2%(50-0% Sudden Change);220Vac±3%(100-0% Sudden Change)
Output Freq. (BAT Mode) 50Hz± 0.2%
Output Waveform Pure Sine Wave
Distortion < 1%(Linear Full Load),< 3%(100% Non-Linear Load)
Overload > 120%: More Than 1 Min
> 150%: 300ms Transfer To Bypass
Crest Ratio 3∶1
Efficiency > 90%
Short-Circuit Circuit Auto Protection, Output Voltage/Current
Output Abnormal INV Output Auto-Locked Protection
Noise Suppression EMI/RFI Wave Filter
BAT Low Shutdown Protection
Dynamic Response 3% At Full Load,Recovering In 20ms
Auto-Restart Available
Software Control Available
Bypass Specification
Static Bypass Transfer Time 0ms
Static Bypass Range 80Vac± 5%~285Vac±5%
Bypass - INV Transfer Time 2ms
Battery Specification
Model OH2010T81600S OH2015T81600S OH2020T81600S
Capacity 10KVA / 8KW 15KVA / 12KW 20KVA / 16KW
Model OH2010T92000S OH2015T92000S OH2020T91600S
Capacity 10KVA / 9KW 15KVA / 13.5KW 20KVA / 18KW
Type Sealed Lead Acid Maintenance Free
VDC 192 Vdc
Charging Current 4 A
Communication Specification
Standard Communication Port Rs232
Optional SNMP/RS485/ Dry Contact
Remote Software Multi-Functional Monitoring System, Online And BAT Mode Status, BAT Fault, Remote Control
Physical Specification
Dimensions In Mm (D×W×H) 190x340x528 238x528x555
Net Weight (Kg) 19 27.5 28