| Model |
OH3010T81607S |
OH3020T82007S |
| Capacity |
10KVA/8KW |
20KVA/16KW |
| Technical Specification |
| UPS Structure |
Online Double Conversion |
| Topology |
High Frequency Online Design |
| Overall Efficiency (AC-AC) |
> 91% |
| Noise (In 2 Meters) |
< 60dB |
| Working Temp. |
-10-40℃ |
| Storage Temp. |
-25 ~ 6 0 ℃( Without Batteries) |
| Humidity |
< 95% Non-Condesing |
| International Standard |
EN 50091-1/2, EN62040-1,EN62040-2 |
| Parallel Redundancy |
Parallel Redundancy Upto 8 Units |
| Protection |
Overload, Short-Circuit, Over Temp., Utility Power Voltage High/Low, BAT Voltage High/Low |
| DC Start |
Available |
| Generator Compatibility |
Available |
| Display |
LCD Display With Multi Information; Output Voltage Selectable:200/208/220/230/240, Output Frequency Selectable:0/50/60Hz; +LED ( Working Diagram) |
| Mute |
Auto |
| Cabinet Standard |
IP20 |
| Cooling System |
Intelligent Speed Control Cooling Fan |
| Elevation |
<1500M,Without Derated |
| Rectifier Specification |
| Input Voltage |
380Vac+N+W |
| Input Voltage Range |
265-494Vac With 100% Full Load, No Load Can Reach 210-494Vac |
| Input Frequency Range |
40-70Hz (Adjustable) |
| Soft-Start |
> 20 Seconds |
| Input PF |
0.99 |
| THDI |
< 5% |
| Output Specification |
| Output Voltage |
Line Voltage: 380×(1±1%)AC Or Phase Voltage: 220×(1±1%)AC |
| Output Power Factor |
0.8 |
| Output Voltage Regulation |
380Vac±1%(Static Load); 380Vac ± 3%(50-0% Sudden Change); 380Vac±5% (100-0% Sudden Change) |
| Output Frequency |
46-54Hz Sync With Utility Grid, More Than The Range Lock At 50Hz, Battery Mode Is 50/60Hz±0.1% |
| Distortion |
< 1%(Linear Full Load),<3%(Non-Linear Full Load) |
| 3 Phase Unbalanced |
Allow 3 Phase 100% Unbalanced |
| Output Volt Unbalanced Degree |
≤1%(Balanced Load); ≤2%(50% Balanced Load) |
| Input/Output Phase Swift |
≤1°(Balanced Load); ≤2°(50% Balanced Load) |
| Frequency Tracking Range |
46Hz to 54Hz |
| Output Waveform |
Pure Sine Wave |
| Overload |
105-125%±5% More Than 1 Minute;> 125-130%±5% More Than 30 Seconds;≥ 135%±5% More Than 300 Ms |
| Crest Ratio |
3∶1 |
| Short-Circuit |
Circuit Auto-Protection, Bypass Switch Tripping |
| Output Abnormal |
INV. Output Auto-Locked Protection |
| Bypass Specification |
| Static Bypass Input Range |
380Vac(-15~+15%) |
| Bypass - INV Transfer Time |
2ms |
| Frequency Tracking Speed |
0.5-2hz/S |
| Manual Maintenance Bypass |
Available |
| Battery Specification |
| Model |
OH2010T81600S |
OH2020T81600S |
| Capacity |
10KVA / 8KW |
20KVA / 16KW |
| Type |
Sealed Lead Acid Maintenance Free |
| VDC - Ah |
192Vdc - 7Ah |
240Vdc - 7Ah |
| Charging Current |
1 Amp |
| BAT Low |
Shutdown Protection |
| Communication Specification |
| Standard Communication Port |
Rs232 |
| Optional |
SNMP/RS485/ Dry Contact |
| Remote Software |
Multi-Functional Monitoring System, Online And BAT Mode Status, BAT Fault, Remote Control |
| Physical Characteristics |
| Dimensions (W×D×H) mm |
260×560×717 |
260×710×717 |
| Net Weight (Kg) |
72 |
98 |
| Note: Product image and technical specifications are for reference and could be change without any notice. |