Model |
OH1001T10207S OH1001T10209S |
OH1002T10407S OH1002T10409S |
OH1003T10607S OH1003T10609S |
OH1006T11607S OH1006T11609S |
OH1010T11607S OH1010T11609S |
Capacity |
1KVA / 1KW |
2KVA / 2KW |
3KVA / 3KW |
6KVA / 6KW |
10KVA / 10KW |
Technical Specifications |
UPS Structure |
Online Double Conversion - Tower Type |
Topology |
High Frequency, Transformer Less |
Overall Efficiency |
> 95%(98.5% under ECO mode) |
Noise(In 2 Meters) |
< 50dB |
Working Temp |
-10℃ to 40℃ |
Storage Temp |
-15 to 60℃(Without BATs) |
Humidity |
< 20-95% Non Condensing |
Safety Standard |
GB/T 7260, GB/T 4943, YD/T1095, TLC |
EMC Standard |
EN/IEC 61000, EN/IEC 62040 |
Protections |
Overload, Short-Circuit, Over Temp., Uti Protections lity Power Voltage High/low, BAT Voltage High/low |
Generator Compatibility |
Available |
DC Start |
Available |
Manual Maintenance Bypass |
None |
Optional |
Display |
LCD Display: Multi-Language with all kinds of messages. Input/ Output /bypass Status, ECO Mode , charging status, load status, Rectifier status, INV. Temp, LED Indicators: UPS States Indicator" |
LCD Display: Multi-Language with all kinds of messages. Input/ Output / bypass Status, ECO Mode , charging status, load status, Rectifier status, INV. Temp, Colored LCD screen:Working (days); SN; Calendar、time;UPS model & structure; Version No.;history log records;history fault records; language set;ECO set; time & calendar set;battery test & so on. LED Indicators: UPS States Indicator |
Alarm |
Mains abnormal or Fault, BAT Voltage High/low, overload、UPS fault, shot circuit etc |
Mute |
Automatic |
ECO Mode |
Available |
EPO Mode |
Available |
Cabinet Standard |
IP20 |
Cooling System |
Intelligent Speed Control Cooling Fan |
Altitude |
<11000M,Without Derated, 1000m <altitude< 4500m, refer to IEC62040 |
Rectifier Specification |
Input Voltage |
220Vac(208/220/230/240Vac available) |
Input Voltage Range |
110-300Vac at 50% load,176-276Vac at 100% loads (±5V) |
Input Frequency Range |
44~56Hz or 54Hz~66Hz ±10Hz (adjustable) |
Input PF |
0.99 |
THDI |
< 3% linear load, < 5% Non-linear load |
Output Specification |
Output Voltage |
220Vac(208/220/230/240Vac available) |
Output PF |
1 |
Output Voltage Regulation |
220Vac±1%(Static Load);220Vac±2%(50-0% Sudden Change);220Vac±5%(100-0% Sudden Change) |
Output Freq. (BAT Mode) |
50Hz±0.1%(Battery mode) |
Output Waveform |
Pure Sine Wave |
Distortion |
< 2%(Linear Full Load),< 4%(100% Non-Linear Load) |
Overload |
Utility mode: 102%~105% load, more than 30mins, 105%~125% load, more than 10mins ,125%~150% load, 30s, >150% load, 500ms Battery mode: 102%~105% load, more than 10mins, 105%~125% load, more than 1mins, 125%~150% load, 10s, >150% load, 500ms |
Crest Ratio |
3:1 |
Efficiency |
> 95% |
Short-Circuit |
Circuit Auto Protection, Output Voltage/Current 0 |
Output Abnormal |
INV Output Auto-Locked Protection |
Noise Suppression |
EMI/RFI Wave Filter |
BAT Low |
Shutdown Protection |
Dynamic Response |
3% At Full Load,Recovering In 20ms |
Auto-Restart |
Available |
Software Control |
Available |
Bypass Specification |
Static Bypass Transfer Time |
0ms |
Static Bypass Range |
80Vac± 5%~285Vac±5% |
Bypass - INV Transfer Time |
< 4ms |
< 2ms |
Battery Specification |
Type |
Sealed Lead Acid Maintenance Free |
VDC-Ah |
24VDC - 7/9Ah |
48VDC - 7/9Ah |
72VDC - 7/9Ah |
192VDC - 7/9Ah |
192VDC - 7/9Ah |
Charging Current |
1A |
Communication Specification |
Standard Communication Port |
Rs232 |
Optional |
SNMP/RS485/ Dry Contact |
Remote Software |
Multi-Functional Monitoring System, Online And BAT Mode Status, BAT Fault, Remote Control |
Physical Parameters |
Dimensions In Mm (D×W×H) |
144×282×214 |
144×397×214 |
190×421×318 |
190×360×670 |
Net Weight Kg |
9 / 10 |
15 / 17 |
20 / 23 |
46 / 54 |
47 / 55 |
Note: Product image and technical specifications are for reference and could be change without any notice. |