Model |
OL1001T80600S |
OL1002T80600S |
OL1003T80800S |
OL1006T81600S OL1006T80800S |
Capacity |
1KVA/0.8KW |
2KVA/1.6KW |
3KVA/2.4KW |
6KVA/4.8KW |
Model |
OL1008T81600S |
OL1010T81600S |
OL1015T81600S |
Capacity |
8KVA/6.4KW |
10KVA/8KW |
15KVA/12KW |
Technical Specification |
UPS Structure |
Online Double Conversion |
Topology |
Low Frequency With Output Isolation Transformer |
Overall Efficiency (AC-AC ) |
> 85% |
Noise(In 2 Meters) |
< 50dB |
Working Temp |
-10-40℃ |
Storage Temp |
-25 ~ 60℃(Without Batteries) |
Humidity |
< 95%Non-Condensing |
Safety Standard |
IEC62040 |
Parallel Redundancy |
Available |
Protections |
Overload, Short-Circuit, Over Temp., Utility Power Voltage High/Low, BAT Voltage High/Low |
DC Start |
Available |
Generator Compatibility |
Available |
Display |
LCD Display |
IP Rating |
IP20 |
Cooling System |
Intelligent Speed Control Cooling Fan |
Elevation |
<1000M,Without Derating |
Rectifier Specification |
Input Voltage |
200/220/230/240Vac Single Phase |
Input Voltage Range |
160-280Vac |
Input Frequency Range |
50Hz±5% |
Soft-Start |
> 20 Seconds |
Output Specification |
Output Voltage |
200/220/230/240Vac |
Output PF |
0.8 |
Output Voltage Regulation |
220Vac±1%( Static Load ),220Vac±2%(50~0% Sudden Change) |
Output Freq |
50Hz±0.1%(BAT Mode) |
Distortion |
<1%(Linear Full Load),< 3%(Non-Linear Full Load) |
Frequency Tracking Range |
46-54Hz |
Output Waveform |
Pure Sine Wave |
Overload |
> 125%: More Than 1 Min; > 150%: More Than 300ms |
> 125%: More Than 10 Mins; > 150%: More Than 1 Min |
Noise Suppression |
EMI/RFI Wave Filter |
Crest Ratio |
3∶1 |
Short-Circuit |
Circuit Auto Protection,Output Voltage/Current 0 |
Output Abnormal |
INV. Output Auto-Locked Protection |
Bypass Specification |
Static Bypass Transfer Time |
0ms |
Static Bypass Range |
220Vac(-15~+15%) |
Frequency Range |
±1Hz, ±2Hz,±3Hz Adjustable |
Bypass - INV Transfer Time |
2ms |
Frequency Tracking Speed |
0.5Hz - 2Hz/s |
Manual Maintenance Bypass |
None |
Available |
Alarm Specification |
Alarm |
Utility Power Fault, BAT Voltage Low, Overload,UPS Fault |
Mute |
Auto |
Battery Specification |
Model |
OL1001T80600S |
OL1002T80600S |
OL1003T80800S |
OL1006T81600S OL1006T80800S |
Capacity |
1KVA/0.8KW |
2KVA/1.6KW |
3KVA/2.4KW |
6KVA/4.8KW |
Model |
OL1008T81600S |
OL1010T81600S |
OL1015T81600S |
Capacity |
8KVA/6.4KW |
10KVA/8KW |
15KVA/12KW |
Type |
Sealed Lead Acid Maintenance Free |
VDC |
72Vdc |
72Vdc |
96Vdc |
192Vdc / 96Vdc |
Charging Current |
5A - Standard 10A-Optional |
5A - Standard 10A-Optional |
5A - Standard 10A-Optional |
5A - Standard 10A-Optional |
VDC |
192Vdc |
192Vdc |
192Vdc |
Charging Current |
5A - Standard 10A-Optional |
5A - Standard 10A-Optional |
5A - Standard 10A-Optional |
BAT Low |
Shutdown Protection |
Communication Specification |
Standard Communication Port |
Rs232 |
Optional |
SNMP/RS485/ Dry Contact |
Remote Software |
Multi-Functional Monitoring System, Online And BAT Mode Status, BAT Fault, Remote Control |
Physical Characteristics |
Dimensions In Mm(W×D×H) |
220×510×395 |
220×610×475 |
Net Weight (Kg) |
22.5 |
23.5 |
29 |
44 |
Dimensions In Mm(W×D×H) |
220×610×715 |
Net Weight (Kg) |
53 |
63 |
70 |
Note:Product Image And Technical Specifications Are For Reference And Could Be Change Without Any Notice. |