Model |
OL3010T93200S |
OL3015T93200S |
OL3020T93200S |
OL3030T93200S |
OL3040T93200S |
Capacity |
10KVA/9KW |
15KVA/13.5KW |
20KVA/18KW |
30KVA/27KW |
40KVA/36KW |
Technical Specification |
UPS Structure |
Online Double Conversion |
Topology |
Low Frequency With Output Isolation Transformer |
Overall Efficiency (AC-AC) |
0.9 |
Noise (In 2 Meters) |
< 50-60dB |
Working Temp. |
25 ~ 60℃ |
Storage Temp. |
25 ~ 60℃ |
Humidity |
< 95%, Non-Condensing |
National Standard |
EN50091-1/IEC950 |
International Standard |
EN 50091-1/2; EN62040-1; EN62040-2 |
Parallel Redundancy |
Available Upto 8 Units |
Protection |
Overload, Short-Circuit, Over Temp., Utility Power Voltage High/Low, BAT Voltage High/Low |
ECO |
Available |
EPO Function |
Available |
DC Start |
Available |
Generator Compatibility |
Available |
Display |
LCD + LED |
Mute |
Auto |
IP Rating |
IP20 |
Cooling System |
Intelligent Speed Control Cooling Fan |
Elevation |
<1500M, Without Derated |
Rectifier Specification |
Input Voltage |
380Vac+N+W(3 Phase + PE) |
Input Voltage Range |
285-475Vac |
Input Frequency Range |
45-65Hz |
Input PF |
0.95( With Input Filter) |
THDI |
<5%(With Optional Accessories) |
Dual Input Availability |
Available(Optional Accessories) |
Input Mis Phase Protection |
Misphase Alarm, UPS Will Not Be Started |
Input Phase Lost Protection |
Phase Lost Alarm, UPS Work On Bypass Mode |
Soft-Start |
> 20 Seconds |
Input Current |
23A |
31A |
39A |
54A |
70A |
Output Specification |
Output Voltage |
Line Voltage: 380×(1±1%)AC Or Phase Voltage: 220×(1±1%)AC |
Output PF |
0.8/0.9 (No Lag) |
Output Voltage Regulation |
380Vac±1%(Static Load);380Vac±2%(50-0% Sudden Change);380Vac±3%(100-0% Sudden Change) |
Output Freq |
±8% At 50Hz: Online Mode Tracking Input And Bypass Freq.; ±0.1%: When Input Or Bypass Frequency Is More Than ±8% Or Under BAT Mode |
THD |
< 1%(Linear Full Load),< 3%(Non-Linear Full Load) |
3 Phase Unbalanced |
Allow 3 Phase 100% Unbalanced |
Output Volt. Unbalanced |
≤1°(Balanced Load); ≤2°(50% Balanced Load) |
Input/Output Phase Swift |
≤1°(Balanced Load); ≤2°(50% Balanced Load) |
Frequency Tracking Range |
45-65Hz |
Output Waveform |
Pure Sine Wave |
Overload |
>125%: More Than 10 Mins; > 150%: More Than 60s Transfer To Bypass |
Crest Ratio |
3∶1 |
Shor T-Circuit |
Circuit Auto-Protection, Bypass Switch Tripping |
Output Abnormal |
INV. Output Auto-Locked Protection |
Bypass Specification |
Static Bypass Transfer Time |
0ms |
Static Bypass Input Range |
380Vac(-15~+15%) |
Frequency Range |
50/60Hz±1Hz, ±2Hz, ±3Hz Adjustable |
Bypass - INV Transfer Time |
2ms |
Frequency Tracking Speed |
0.5-2hz/S |
Maintenance Bypass |
Available |
Battery Specification |
Model |
OL3010T93200S |
OL3015T93200S |
OL3020T93200S |
OL3030T93200S |
OL3040T93200S |
Capacity |
10KVA/9KW |
15KVA/13.5KW |
20KVA/18KW |
30KVA/27KW |
40KVA/36KW |
Charging Methods |
DSP Controlled Charger: Equalized/Pulse Charge, Float Charge, Intelligent Battery Management |
Type |
Sealed Lead Acid Maintenance Free |
VDC |
336-384VDC |
Float Charge Voltage |
438Vdc |
Charging Current |
5-10A |
Abnormal Protections |
BAT Over-Charged, Emergency Charger Shutdown Protection Or UPS Shutdown Protection |
Communication Specification |
Standard Communication Port |
Rs232 |
Optional |
SNMP/RS485/ Dry Contact |
Remote Software |
Multi-Functional Monitoring System, Online And BAT Mode Status, BAT Fault, Remote Control |
Physical Characteristics |
Size In Mm (W×H×D) |
475×990×700 |
550×1200×800 |
Net Weight (Kg) |
210 |
223 |
230 |
280 |
330 |
Note:Product image and technical specifications are for reference and could be change without any notice. |