| Model |
OL1001R80600S |
OL1002R80600S |
OL1003R80800S |
OL1006R81600S / OL1006R80800S |
OL1008R81600S |
OL1010R81600S |
| Capacity |
1KVA/0.8KW |
2KVA/1.6KW |
3KVA/2.4KW |
6KVA/4.8KW |
8KVA/6.4KW |
10KVA/8KW |
| Technical Specification |
| UPS Structure |
Online Double Conversion |
| Topology |
Low Frequency With Output Isolation Transformer |
| Overall Efficiency (AC-AC ) |
> 85% |
| Noise(In 2 Meters) |
< 50dB |
| Working Temp |
-10-40℃ |
| Storage Temp |
-25 ~ 60℃(Without Batteries) |
| Humidity |
< 95%Non-Condensing |
| Safety Standard |
IEC62040 |
| Parallel Redundancy |
Available |
| Protections |
Overload, Short-Circuit, Over Temp., Utility Power Voltage High/Low, BAT Voltage High/Low |
| DC Start |
Available |
| Generator Compatibility |
Available |
| Display |
LCD Display |
| IP Rating |
IP20 |
| Cooling System |
Intelligent Speed Control Cooling Fan |
| Elevation |
<1000M,Without Derating |
| Rectifier Specification |
| Input Voltage |
200/220/230/240Vac Single Phase |
| Input Voltage Range |
160-280Vac |
| Input Frequency Range |
50Hz±5% |
| Soft-Start |
> 20 Seconds |
| Output Specification |
| Output Voltage |
200/220/230/240Vac |
| Output PF |
0.8 |
| Output Voltage Regulation |
220Vac±1%( Static Load ),220Vac±2%(50~0% Sudden Change) |
| Output Freq |
50Hz±0.1%(BAT Mode) |
| Distortion |
<1%(Linear Full Load),< 3%(Non-Linear Full Load) |
| Frequency Tracking Range |
46-54Hz |
| Output Waveform |
Pure Sine Wave |
| Overload |
> 125%: More Than 1 Min; > 150%: More Than 300ms |
> 125%: More Than 10 Mins; > 150%: More Than 1 Min |
| Noise Suppression |
EMI/RFI Wave Filter |
| Crest Ratio |
3∶1 |
| Short-Circuit |
Circuit Auto Protection,Output Voltage/Current 0 |
| Output Abnormal |
INV. Output Auto-Locked Protection |
| Bypass Specification |
| Static Bypass Transfer Time |
0ms |
| Static Bypass Range |
220Vac(-15~+15%) |
| Frequency Range |
±1Hz, ±2Hz,±3Hz Adjustable |
| Bypass -> INV Transfer Time |
2ms |
| Frequency Tracking Speed |
0.5-2hz/S |
| Manual Maintenance Bypass |
None |
Available |
| Alarm Specification |
| Alarm |
Utility Power Fault, BAT Voltage Low, Overload,UPS Fault |
| Mute |
Auto |
| Battery Specification |
| Model |
OL1001R80600S |
OL1002R80600S |
OL1003R80800S |
OL1006R81600S / OL1006R80800S |
OL1008R81600S |
OL1010R81600S |
| Capacity |
1KVA/0.8KW |
2KVA/1.6KW |
3KVA/2.4KW |
6KVA/4.8KW |
8KVA/6.4KW |
10KVA/8KW |
| Type |
Sealed Lead Acid Maintenance Free |
| VDC |
72Vdc |
72Vdc |
96Vdc |
192Vdc / 96Vdc |
192Vdc |
192Vdc |
| Charging Current |
5A - Standard 10A-Optional |
5A - Standard 10A-Optional |
5A - Standard 10A-Optional |
5A - Standard 10A-Optional |
5A - Standard 10A-Optional |
5A - Standard 10A-Optional |
| BAT Low |
Shutdown Protection |
| Communication Specification |
| Standard Communication Port |
Rs232 |
| Optional |
SNMP/RS485/ Dry Contact |
| Remote Software |
Multi-Functional Monitoring System, Online And BAT Mode Status, BAT Fault, Remote Control |
| Note: Product image and technical specifications are for reference and could be change without any notice. |