Model |
OH1001R11200L |
OH1002R12300L |
OH1003R13000L |
OH1006R16000L |
OH1010R16000L |
Capacity |
1KVA/1KW |
2KVA/2KW |
3KVA/3KW |
6KVA/6KW |
10KVA/10KW |
Technical Specifications |
UPS Structure |
Online Double Conversion - Rack Mount Type |
Topology |
High Frequency, Transformer Less |
Overall Efficiency |
> 95% (under ECO mode the overall efficiency upto 98.5%) |
Noise(In 2 Meters) |
< 50dB |
Working Temperature |
0-50℃ |
Storage Temperature |
-15 ~ 60℃(Without batteries) |
Humidity |
< 95% Non Condensing |
Safety Standard |
GB/T 7260, GB/T 4943, YD/T1095, TLC |
EMC Standard |
EN/IEC 61000, EN/IEC 62040 |
Protections |
Overload, Short-Circuit, Over Temp., Utility Power Voltage High/Low, BAT Voltage High/Low |
Alarm |
Mains abnormal or Fault, BAT Voltage High/low, overload、UPS fault, shot circuit etc |
Generator Compatibility |
Available |
DC Start |
Available |
Manual Maintenance Bypass |
None |
Optional |
Display |
LCD Display: Multi-Language with all kinds of messages. Input/ Output /bypass Status, ECO Mode, charging status, load status, Rectifier status, INV. Temp, Colored LCD screen; Working (days); SN; Calendar; time; UPS model & structure; Version No.; history log records;history fault records; language set; ECO set; time & calendar set; battery test & so on. LED Indicators: UPS States Indicator |
Alarm |
Auto / Manual |
Mute |
Auto |
ECO / EPO |
Optional |
Rectifier Specification |
Input Voltage |
220Vac (208/220/230/240Vac optional) |
Input Voltage Range |
110~300Vac |
Input Frequency Range |
44~56Hz or 54Hz~66Hz,±10Hz |
Input PF |
0.99 |
THDI |
<= 4% linear load, 6% Non-linear load |
Output Specification |
Output Voltage |
220Vac (208/220/230/240Vac Optional) |
Output PF |
1 |
Output Voltage Regulation |
220Vac±1%(Static Load);220Vac±2%(50-0% Sudden Change); 220Vac±5%(100-0% Sudden Change) |
Output Freq. (BAT Mode) |
50Hz±0.1% |
Output Waveform |
Pure Sine Wave |
Distortion |
< 1%(Linear Full Load),< 3%(100% Non-Linear Load) |
Overload |
102%~110% load 30mins 110%~125% load 10mins 125%~150% load 500ms |
102%~110% load 30mins Bypass 110%~130% load 10mins Bypass 130%~150% load 30s Bypass >=150% 500ms Bypass |
Crest Ratio |
3∶1 |
Efficiency |
> 95% |
Short-Circuit |
Circuit Auto Protection, Output Voltage/Current 0 |
Output Abnormal |
INV Output Auto-Locked Protection |
Noise Suppression |
EMI/RFI Wave Filter |
BAT Voltage Low |
Shutdown Protection |
Dynamic Response |
3% At Full Load,Recovering In 20ms |
Auto-Restart |
Available |
Software Control |
Available |
Bypass Specification |
Static Bypass Transfer Time |
0ms |
Static Bypass Range |
80Vac± 5%~285Vac±5% |
Bypass - INV Transfer Time |
2ms |
Battery Specification |
Type |
Lithium-ion Battery Pack |
Nominal Voltage / Cell Qty |
38.4Vdc / 12s |
73.6Vdc / 23s |
96Vdc / 30s |
192Vdc / 60s |
192Vdc / 60s |
Equilized Charging Voltage |
43.2Vdc |
82.8Vdc |
108Vdc |
216Vdc |
216Vdc |
Charging Current |
12A |
Communication Specification |
Standard Communication Port |
Rs232 |
Optional |
SNMP/RS485/ Dry Contact |
Lithium-ion pack Communication Port |
Multi-functional Monitoring System, power and battery status, power failure, low battery voltage, remote shutdown, control menu |
UPS Physical Parameters |
Dimensions In Mm (D×W×H) |
400×440×88/2U |
470×440×88/2U |
Net Weight Kg |
5.5 |
7.5 |
8.0 |
10.0 |
10.5 |
Battery Pack Physical Parameters |
25Ah dimensions (D×W×H) |
400×440×8 8/2U |
450×440×176/4U |
480×440×220/5U |
Net Weight Kg |
19 |
30 |
60 |
60 |
50Ah dimensions (D×W×H) |
500×440×220/5U |
500×440×220/5U 480×440×160 |
Net Weight Kg |
55 |
110 |
100Ah dimensions (D×W×H) |
500×440×220/5U 480×440×160 |
400×440×132/3U 600×440×220/5U×2 |
Net Weight Kg |
110 |
230 |
Note: Product image and technical specifications are for reference and could be change without any notice. |