| Model |
OH1001C10300S |
OH1002C10600S |
OH1003C10800S |
OH1006C11600S |
OH1010C11600S |
| Capacity |
1KVA / 1KW |
2KVA / 2KW |
3KVA / 3KW |
6KVA / 6KW |
10KVA / 10KW |
| Technical Specification |
| UPS Structure |
Online Double Conversion - Rack / Tower Type |
| Topology |
High Frequency, Transformer Less |
| Overall Efficiency (AC-AC ) |
> 95%(98.5% under ECO mode) |
| Noise(In 2 Meters) |
< 50dB |
| Working Temp |
-10 - 40°C |
| Storage Temp |
-15 ~ 60℃(Without BATs) |
| Humidity |
< 20-95% Non-Condensing |
| Safety Standard |
GB/T 7260, GB/T 4943, YD/T1095, TLC |
| EMC Standard |
EN/IEC 61000, EN/IEC 62040, |
| Protections |
Overload, Short-Circuit, Over Temp., Utility Power Voltage High/Low, BAT Voltage High/Low |
| Generator Compatibility |
Available |
| DC Start |
Available |
| Manual Maintenance Bypass |
NA |
Optional |
| Display |
LCD Display: Multi-Language with all kinds of messages. Input/ Output /bypass Status, ECO Mode , charging status, load status, Rectifier status, INV. Temp, LED Indicators: UPS States Indicator |
LCD Display: Multi-Language with all kinds of messages. Input/ Output /bypass Status, ECO Mode , charging status, load status, Rectifier status, INV. Temp, Colored LCD screen:Working (days);SN; Calendar、time;UPS model & structure; Version No.;history log records;history fault records;language set;ECO set; time & calendar set;battery test & so on. LED Indicators: UPS States Indicator |
| Alarm |
Mains abnormal or Fault, BAT Voltage High/low, overload、UPS fault, shot circuit etc |
| ECO mode |
Available |
| EPO mode |
Available |
| Mute |
Auto |
| Cabinet Standard |
IP20 |
| Cooling System |
Intelligent Speed Control Cooling Fan |
| Altitude |
<11000M,Without Derated, 1000m <altitude< 4500m, refer to IEC62040 |
| Rectifier Specification |
| Input Voltage |
220Vac(208/220/230/240Vac available) |
| Input Voltage Range |
110-300Vac at 50% load,176-276Vac at 100% loads (±5V) |
| Input Frequency Range |
44~56Hz or 54Hz~66Hz ±10Hz (adjustable)) |
| Input PF |
0.99 |
| THDI |
<=3% linear load,<=5% Non-linear load |
| Output Specification |
| Output Voltage |
220Vac(208/220/230/240Vac available) |
| Output PF |
1 |
| Output Voltage Regulation |
220Vac±1%(Static Load);220Vac±2%(50-0% Sudden Change);220Vac±5%(100-0% Sudden Change) |
| Output Freq. (BAT Mode) |
50Hz±0.1%(Battery mode) |
| Output Waveform |
Pure Sine Wave |
| Distortion |
< 2%(Linear Full Load),< 4%(100% Non-Linear Full Load)) |
| Overload |
Utility Mode: 102%~105% load, more than 30mins, 105%~125% load, more than 10mins ,125%~150% load, 30s, >150% load, 500ms |
Battery mode:102%~105% load, more than 10mins, 105%~125% load, more than 1mins, 125%~150% load, 10s, >150% load, 500ms |
| Crest Ratio |
3:1 |
| Inverter Efficiency |
> 95% |
| Short-Circuit |
Circuit Auto Protection, Output Voltage/Current 0 |
| Output Abnormal |
INV Output Auto-Locked Protection |
| Noise Suppression |
EMI/RFI Wave Filter |
| Battery voltage low |
Shutdown Protection |
| Dynamic Response |
3% At Full Load,Recovering In 20ms |
| Auto-Restart Function |
Available |
| Software Control |
Available |
| Bypass Specification |
| Static Bypass Transfer Time |
0ms |
| Static Bypass Range |
80Vac± 5%~285Vac±5% |
| Bypass - INV Transfer Time |
< 4ms |
< 2ms |
| Battery Specification |
| Type |
Sealed Lead Acid Maintenance Free |
| VDC |
36 |
72 |
96 |
192 |
192 |
| Charging Current |
5-10A |
6-12A |
| Communication Specification |
| Standard Communication Port |
Std.RS232/EPO;SNMP/485/dry contact (optional) |
| Optional |
SNMP/RS485/ Dry Contact |
| Remote Software |
Multi-functional Monitoring System, Online and BAT Mode Status, utility fault, BAT Fault, Remote Control |
| Physical Parameters |
| Dimensions in mm (WxDxH) |
440×450×88/2U |
440×470×88/2U |
| Net Weight (Kg) |
5 |
7 |
8 |
10 |
10.5 |
| Note: Product image and technical specifications are for reference and could be change without any notice. |