| Cabinet Model |
MH3090U94000S |
MH3150U94000S |
MH3300U94000S |
| Cabinet Capacity In (KVA) |
90KVA |
150KVA |
300KVA |
| Module |
MH3030M90000S |
| Module Capacity |
30KVA/27KW |
| Host Machine Specification |
| UPS Structure |
Online Double Conversion |
| Appearance |
Standard Telecomm Cabinet With Modular Structure Design |
| Overall Efficiency |
> 95% |
| Noise(In 2 Meters) |
< 50-65dB |
| Working Temp. |
0-40℃ |
| Storage Temp. |
-25 ~ 55℃(Without Batteries) |
| Humidity |
< 95% Non-Condensing |
| Safety Standard |
IEC62040 |
| EMC Standard |
CE,YD/T1095-2008,EN /IEC 62040-2,EN/IEC 62040-1-1 |
| Parallel Redundancy |
Modular Parallel Upto 10 Units |
| Protection |
Overload, Short-Circuit, Over Temp., Utility Power Voltage High/Low, BAT Voltage High/Low |
| DC Start |
Available |
| Generator Compatibility |
Available |
| Display |
LCD |
| Mute |
Auto |
| IP Rating |
IP20 |
| Cooling System |
Intelligent Speed Control Cooling Fan |
| Elevation |
<1000M Without Derating >1000M: Derating 1% Every 100M |
| Rectifier Specification |
| Input Voltage |
380Vac+N+W, 3 Phase |
| Input Voltage Range |
208-478Vac |
| Input Frequency Range |
40-70Hz |
| Soft-Start |
> 60 Seconds |
| Input PF |
0.99 |
| THDI |
≤ 3%(100% Non-Linear Load) |
| Output Specification |
| Output Voltage |
Line Voltage: 380×(1±1%)AC Or Phase Voltage: 220×(1±1%)AC |
| Output Power Factor |
0.9 |
| Output Voltage Regulation |
380Vac±1%(Static Load);380Vac±2%(50-0% Sudden Change);380Vac±3%(100-0% Sudden Change) |
| Output Frequency |
Synchronization With Input At Online Mode. When Differences Are Greater Than ±10% (Selectable±1%,2%,4%,5%) Output Freq. Will Be 50×(±0.2)Hz 50Hz±0.2% (BAT Mode) |
| Distortion |
<2%(Linear Full Load); < 5%(Non-Linear Full Load) |
| 3 Phase Unbalanced |
Allow 3 Phase 100% Unbalanced |
| Output Volt. Unbalanced Degree |
≤1°(Balanced Load),≤2°(50% Balanced Load) |
| Input/Output Phase Swift |
≤1°(Balanced Load),≤2°(50% Balanced Load) |
| Frequency Tracking Range |
47-63Hz |
| Output Waveform |
Pure Sine Wave |
| Overload |
110%: More Than 10 Mins |
| |
> 125%: More Than 1 Min; |
| |
> 150%: More Than 30 Seconds Then Transfer To Bypass |
| Crest Ratio |
3∶1 |
| Efficiency |
> 95% |
| Short-Circuit |
Circuit Auto-Protection, Bypass Switch Tripping |
| Output Abnormal |
INV. Output Auto-Locked Protection |
| Bypass Specification |
| Static Bypass Transfer Time |
0ms |
| Static Bypass Input Range |
Bypass Protection Upper Limit:+15% (Adjustable +5%、+10%、+25%) Bypass Protection Lower Limit: - 4 5 % ( Adjustable - 2 0 %、 - 3 0 % ) Bypass Frequency Protection Range:±10% |
| Frequency Range |
±1Hz, ±2Hz, ±3Hz Adjustable |
| Bypass - INV Transfer Time |
2ms |
| Frequency Tracking Speed |
0.5-2hz/S |
| Manual Maintenance Bypass |
Available |
| Battery Specification |
| Cabinet Model |
MH3090U94000S |
MH3150U94000S |
MH3300U94000S |
| Cabinet Capacity In (KVA) |
90KVA |
150KVA |
300KVA |
| Module |
MH3030M90000S |
| Module Capacity |
30KVA/27KW |
| Type |
Sealed Lead Acid Maintenance Free |
| BAT Rated Volts/Units |
±192V\±204V\±216V\±228V\±240V DC |
| Charging Current / Module |
10Amax |
| BAT Low |
Shutdown Protection |
| Communication Specification |
| Communication Port |
RS232/SNMP/485/ Dry Contact(Optional Accessory) |
| Remote Software |
Multi-Functional Monitoring System, Online And BAT Mode Status, BAT Fault, Remote Control |
| Physical Characteristics |
| Module Size Mm (W×D×H) |
443×580×131/3U |
| Cabinet Size Mm (W×D×H) |
600×840×1400 |
600×840×1400 |
600×1100×2000 |
| Module Net Weight (Kg) |
33 |
| Cabinet Net Weight (Kg) |
157 |
169 |
306 |
| Note: Product image and technical specifications are for reference and could be change without any notice. |