The i-power T-7601 series is a full-digital DSP control 48Vdc inverter power equipment. It can be widely used in telecommunication, network, computers, office, automation equipment, and other areas to provide stable and reliable high quality AC power. It achieves voltage and frequency stabilization of high-quality pure sine wave power supply with 19’’ 2U rack-mount structure, which is a perfect selection for Telecomm industry.
Product Highlights:
Multi LCD Display with LED indicators
Ability to switch ON the system directly
USB/RS232 & RJ-11/RJ45 serial port interface (Optional).
All devices are fully tested and verified for maximum performance.
Auto restart (when mains power is restored, after discharge of the batteries)
Model |
IH1X50R80400T |
IH1001R80400T |
IH1002R80400T |
IH1003R80400T |
IH1004R80400T |
Capacity |
0.5KVA |
1KVA |
2KVA |
3KVA |
4KVA |
Technical Specifications |
Backfill noise current |
<=10% |
Bypass voltage range(Vac) |
220±20% |
Rated Input current (A) |
1.8 |
3.6 |
7.2 |
10.8/td> |
14.5 |
Bypass switching time(ms) |
<=5ms |
Rated output (W) |
400 |
800 |
1600 |
2400/td> |
3200 |
Output voltage & frequency |
220Vac,50Hz |
Output voltage accuracy(V) |
220±3% |
Precision of output freq. (Hz) |
50±0.1% |
THD |
<=3%(linear load) |
Dynamic response |
5% (load 25%←→100%) |
Power factor (PF) |
0.8 |
Overload |
>=100%~125%,10; 125%~150%,15; 150%,Immediately shut off |
Inverter efficiency |
>=85%(80% Resistive load) |
Noise(1 Meter) |
<=65dB |
Environment temperature |
-25℃~+50℃ |
Humidity |
0~90%,Non-condensate |
Max Altitude(m) |
<=1000 |
Rated input Vdc |
48 VDC |
Input voltage range (Vdc) |
Working voltage 40V—58.8V Boot voltage 42V--57V |
Rated Input Current A |
9.8 |
19 |
38 |
57 |
77 |
Note: Rated output power deviation:500VA±50W;1-10KVA±100W |
Note: Product image and technical specifications are for reference purpose and could be change without any notice. |
Model |
IH1005R80400T |
IH1006R80400T |
IH1008R80400T |
IH1010R80400T |
Capacity |
5KVA |
6KVA |
8KVA |
10KVA |
Technical Specifications |
Backfill noise current |
<=10% |
Bypass voltage range(Vac) |
220±20% |
Rated Input current (A) |
18.2 |
21.8 |
29 |
36/td> |
Bypass switching time(ms) |
<=5ms |
Rated output (W) |
4000 |
4800 |
6400 |
8000/td> |
Output voltage & frequency |
220Vac,50Hz |
Output voltage accuracy(V) |
220±3% |
Precision of output freq. (Hz) |
50±0.1% |
THD |
<=3%(linear load) |
Dynamic response |
5% (load 25%←→100%) |
Power factor (PF) |
0.8 |
Overload |
>=100%~125%,10; 125%~150%,15; 150%,Immediately shut off |
Inverter efficiency |
>=85%(80% Resistive load) |
Noise(1 Meter) |
<=65dB |
Environment temperature |
-25℃~+50℃ |
Humidity |
0~90%,Non-condensate |
Max Altitude(m) |
<=1000 |
Rated input Vdc |
48 VDC |
Input voltage range (Vdc) |
Working voltage 40V—58.8V Boot voltage 42V--57V |
Rated Input Current A |
9.8 |
19 |
38 |
57 |
77 |
Note: Rated output power deviation:500VA±50W;1-10KVA±100W |
Note: Product image and technical specifications are for reference purpose and could be change without any notice. |