42U Rack
|
Cabinet
|
42U cabinet *1, top plate *1 (top plate is perforated with brush), angle gauge *4(42U), depth support *2
|
Front door
|
Tempered glass door 4mm, single-opened, with electromagnetic lock *3 (12V with feedback), door spring *1, and password lock
|
Rear door
|
Rear door metal sheet double opening, equipped with electromagnetic lock (12V with feedback), electromagnetic lock switch button *1, door spring *1
|
Wind deflector
|
Left and right windshields, upper and lower windshields, and left and right windshields are affixed with sealing strips
|
Base board
|
The whole bottom plate is provided with a cover plate through a wire hole
|
Cotton insulation
|
10mm insulating cotton with adhesive foil
|
Illuminate
|
Equipped with front and rear lighting
|
PDU bracket
|
Unilateral single, 2 PCs set
|
side plate
|
Left and right side plates
|
Vertical wiring board
|
Left and right vertical wiring boards
|
1U quick installation blind plate
|
1U quick installation blind plate
|
L-shaped bracket
|
Left and right L-shaped brackets
|
Bearing plate
|
bearing 150Kg
|
Transport wheel
|
4 pcs/set (non-load bearing wheels)
|
Dimensions
|
600*1200*2000mm/42U, 200mm cold aisle
|
Power Distribution module
|
Standard Configuration
|
1, not less than 6KVA power distribution
|
2. AC input: 80A/2P
|
3. generator input: 80A/2P
|
4. Lightning arrester: 20KA/2P(L+N)
|
5. Repair bypass switch: 63A/2P
|
6. UPS input switch: 16A/1P
|
7. UPS output switch: 16A2/P
|
8、PDU1:16A/1P
|
9、PDU2:16A/1P
|
9. Air conditioner: 10A/1P
|
10. reserved switch *2 : 10A/1P and 16A/1P
|
Function
|
1. detect the voltage, current, active power, power factor and load%
|
2. Detect the voltage, current, power, load factor, electric energy and power factor of the output switch
|
3. Detect the state of the input switch
|
4. Lightning protection alarm
|
5, RS485 connection moving ring monitoring
|
6. With buzzer and LED indication
|
7. DC power supply 220Vdc/12Vdc-7A
|
8. LCD screen
|
Dimensions
|
440×540×132mm3U
|
PDU
|
Standard non-intelligent vertical installation
|
16A single phase, 12 *C13+4 * c19 (1.5m cable)
|
Dimensions
|
60×880×45mm
|
UPS power supply
|
Item
|
Specification
|
Rated Capacity
|
6KVA/6KW
|
Input
|
Input
|
L+N+PE (single phase)
|
rated voltage
|
220Vac
|
voltage range
|
110~300VAC
|
frequency
|
50/60Hz
|
power factor
|
≥0.99
|
Output
|
Output
|
L+N+PE (single phase)
|
Rated voltage
|
220Vac
|
Output accuracy
|
±1%
|
Power factor
|
1
|
Frequency
|
50/60±0.1Hz
|
Harmonic wave
|
Linear load≤2, nonlinear load≤5 (PF=0.8)
|
Overload capacity
|
102%~110% 30 minutes to bypass; 110%~130% 10 minutes to bypass; 130%~150% 30 seconds turn bypass; ≥150% 500ms turn to bypass.
|
Crest ratio
|
3:01
|
Efficiency
|
Mains mode
|
100% load ≥ 95%
|
change over
|
Mains inverter-bypass
|
0ms
|
time
|
Bypass-inverter
|
2ms
|
Battery and charger
|
Battery type
|
lead-acid maintenance free
|
Battery qty
|
16pcs
|
charging voltage
|
218.5Vdc
|
charging current
|
1-10A
|
Smart slot
|
RS232, SNMP card, RS485, dry contact
|
Short circuit protection
|
available
|
Noise (dB)
|
< 50db (1m)
|
Standards and certifications
|
EN/IEC 61000, EN/IEC 62040, GB/T 7260, GB/T 4943, YDT1095, TLC, etc
|
Dimensions
|
440×470×88mm/2U
|
Battery
|
Lead-acid maintenance-free battery
|
Matching different capacities according to customer requirements
|
Air-conditioning system
|
Model number in cabinet
|
IC-003 cabinet, rack structure
|
Machine current a in full-load cabinet
|
13.9
|
Cooling capacity
|
3.9kW
|
Sensible heat ratio%
|
95
|
Air volume -m3/h
|
700
|
Input voltage and frequency
|
220Vac/50Hz
|
Functional description
|
3.9kW precision air conditioning, rack mounted, single cooling type, including outdoor unit. The refrigeration capacity of the variable frequency compressor is dynamically adjusted to avoid condensation, air volume of internal and external EC fans automatically adjust. built-in refrigerant pressure and temperature sensor and electronic expansion valve
|
Dimensions (internal)
|
440×828×266mm/6U
|
Dimensions Outdoor unit
|
800×395×632mm
|
Monitoring System
|
Monitoring range
|
JEMS host: Monitor the running status of power distribution, UPS , air conditioner, temperature and humidity, smoke, water leakage, access control, etc.
|
Dimensions
|
440×80×44mm1U
|
Monitor
|
10 "touch screen, installed on the front glass door
|
Environmental sensor
|
Smoke detector
|
Working voltage: DC 9~24V
|
Standby current: 10uA
|
Alarm current: ≤15mA (with buzzer alarm and indicator lamp alarm)
|
Alarm indication: red LED light flashes
|
Ambient temperature: max.95% RH (no condensation)
|
Signal output: dry contact output of switch output relay
|
Sensitivity to spirit: 0.5dbm (0.1dbm)
|
Overall dimensions: 100mm (diameter) *-55mm (height)
|
Temperature and humidity sensor
|
Operating voltage: 2.15-5.5V
|
Output signal: IIC digital signal
|
Humidity measurement range: 0…100% RH
|
Temperature measurement range: -40…125
|
Accuracy: 2% RH 0.2
|
IIC address: OX44
|
Water leakage detection sensor
|
Working voltage: 12Vdc (9-16Vdc) with polarity protection, and the length of detection line is 1.5m.
|